The tools will run about 12% slower than their normal speed.
Ensure that you do not accidentally feed 220V into the tools. (I am assuming that you are taking the 220V feed and powering the tools via the yellow transformers?
Also be aware that of the generator is 220V 3 phase, you need to take the power between either red/yellow/blue and neutral. If you go between the phases (i.e. any combination of red+blue etc) you will get around 380 v. After the transformer that will give you 170V, which is too much for power tools.
Regards
Mark Hawkins